Product Description
Our ac metal enclosed switchgear is designed for primary medium-voltage distribution where operating safety, circuit separation, mechanical interlocking, and maintenance access are essential. The KYN40.5(Z)/T1600-31.5 configuration is a 40.5 kV class metal-enclosed system with a rated current of 1600 A and a short-circuit breaking rating of 31.5 kA, as indicated by the model designation. It can be arranged for incoming lines, outgoing feeders, bus sectionalizing, transformer protection, metering, and station service according to the project single-line diagram. The ac metal enclosed switchgear uses a compartmentalized cabinet structure to organize the circuit breaker, busbar, cable, and low-voltage control areas. This separation supports safer inspection and helps prevent one functional area from becoming an uncontrolled access path to another. Interlocks can be engineered to coordinate breaker position, isolation, earthing, and door access so that normal operating sequences are clear to trained personnel. The cabinet layout also considers lifting, transport, on-site joining, cable termination, and maintenance space, which are critical in high-voltage rooms where installation errors are costly to correct.

Jiangsu Guoxing Electric Equipment Co., Ltd. manufactures ac metal enclosed switchgear with factory-direct control over the enclosure, internal assembly, wiring, inspection, and documentation. The company has operated since 1984 and maintains a 36,000-square-meter facility with more than 200 sets of production and test equipment. CNC sheet-metal processing supports dimensional accuracy, while the test center includes equipment for electrical performance, surge, transient, electrostatic-discharge, high- and low-temperature, salt-spray, and dust-rain verification for applicable product lines. The ac metal enclosed switchgear can be customized with specified vacuum circuit breakers, protection relays, current and voltage transformers, meters, communication devices, arc-detection options, and cable interfaces. We can manufacture from technical drawings or develop the arrangement from a customer specification. Before packing, every cabinet undergoes 100% inspection and an inspection record can be supplied. Third-party inspection is accepted when the buyer provides the relevant standard and technical requirements. For agents and engineering companies, this creates a clear chain of responsibility from design review through production, testing, packing, and after-sales support.
Specifications
|
Parameter |
Specification |
|
Model / Series |
KYN40.5(Z)/T1600-31.5 AC metal-enclosed switchgear |
|
Rated Voltage |
40.5 kV |
|
Rated Current |
1600 A |
|
Rated Short-Circuit Breaking Current |
31.5 kA |
|
Installation |
Indoor, floor-standing, multi-panel lineup |
|
Structure |
Metal-enclosed, compartmentalized, withdrawable circuit-breaker arrangement |
|
Typical Functions |
Incoming, feeder, bus section, transformer protection, metering, and control |
Applications
Primary Substations
Incoming and outgoing feeder control in industrial and utility substations.
Large Industrial Facilities
Distribution for mining, metallurgy, chemical, cement, and heavy manufacturing plants.
Energy Projects
Medium-voltage distribution in power generation, renewable energy, and grid-support facilities.
Infrastructure Systems
Power distribution for transport, water, municipal, and large public projects.
Factory Strength
The factory has extensive experience in high- and low-voltage electrical equipment, complete switchgear, and distribution systems. An independent R&D team and cooperation with electrical research institutions support product engineering and application development.
More than 200 sets of production and test equipment help control cabinet fabrication, assembly accuracy, component consistency, and final verification.
Quality Control
Quality control follows the approved technical specification and product inspection file. Checks include cabinet dimensions, compartment structure, breaker operation, interlocks, earthing, busbar and conductor installation, secondary wiring, insulation, and functional logic.
Each unit is inspected before packing. Inspection records can be provided, and third-party witness inspection is supported against agreed acceptance criteria.
Certifications & Compliance
The company maintains ISO and ISO14001 management certification and holds CCC, CQC, CCS, and QC080000 credentials for applicable products and activities.
Project certification and test documentation are confirmed according to the exact switchgear configuration, component brands, destination market, and contract requirements.
Hot Tags: ac metal enclosed switchgear, China ac metal enclosed switchgear manufacturers, factory, Electrical Distribution Application Box, High Voltage Electrical Protection Equipment, High Voltage Power Safety Equipment, High Voltage Utility Distribution System, High Voltage Vacuum Switchgear, Power Distribution Network Cabinet